Current position: Home > First Class Fire Engineer > Preparation Materials for First Class Fire Engineer > 2020 Comprehensive Capability Examination for First Class Fire Engineer: Fire Pump Water Outlet and Suction Pipe

Examination points for comprehensive capabilities of first-class fire engineers in 2020: fire pump water outlet pipes and suction pipes

点击量: Release time: January 9, 2020 13:27:10 Source: Global Online School Traffic:

First-level fire engineer registration, examination, check time, free SMS reminder

area

    Get VerifiedBook Now

    Please fill in the picture verification code to get the SMS verification code

    Can't see clearly, change a picture

    Get SMS Verification Code for Free

    [Abstract] 2020 first-level fire engineer exam preparation has begun, Global Network School has organized the "2020 Comprehensive Test Capability of First-rate Fire Engineers" for you. For more test preparation materials, simulated test questions, and real questions over the years, please continue to pay attention to Global Online School One. Grade Fire Engineer Exam Channel!

    Related Recommendations: Summary of Lecture Notes on Comprehensive Capabilities of First Class Fire Engineers in 2020

    Fire pump outlet pipe and suction pipe

    straw

    ① For a group of fire pumps, the number of suction pipes should not be less than two. When one of them is damaged or overhauled, the remaining suction pipes should still be able to pass through the entire fire water supply design flow.

    ② The suction pipe of the fire pump should be arranged to avoid the formation of air bags.

    ③ The submersion depth of the fire pump suction inlet should meet the safety requirements of the fire pump operation at the lowest water level. The submersion depth of the suction pipe bell mouth at the lowest effective water level of the fire fighting pool should not be less than 600mm. Should be less than 200mm.

    ④ When the suction pipe of the fire pump passes through the fire water tank, a flexible sleeve shall be used. When a steel waterproof sleeve is used, a flexible joint shall be provided on the pump suction pipe, and the pipe diameter shall not be greater than DN150mm.

    ⑤ The suction pipe of the fire pump should be equipped with a bright-stem gate valve or a butterfly valve with a self-locking device. When a dark-stem valve is installed, an opening scale and a mark should be provided. When the pipe diameter exceeds DN300, an electric valve should be installed.

    ⑥ When the diameter of the suction pipe is less than DN250, the velocity should be 1.0 ~ 1.2m / s; when the diameter is greater than DN250, it should be 1.2 ~ 1.6m / s.

    布置 The layout of the suction wells should be such that the water flow in the wells is smooth and the flow velocity is uniform without vortices.

    管道 The pipe of the fire pump can be equipped with a pipe filter. The water passing area of the pipe filter should be greater than 4 times the water passing area of the pipe, and the hole diameter should not be less than 3 mm.

    气囊 There should be no airbags and air leaks on the horizontal pipe section of the suction pipe of the fire pump (flat top with eccentric reducer).

    ⑩ A vacuum gauge, pressure gauge or vacuum pressure gauge should be installed on the suction pipe of the fire pump. The maximum range of the pressure gauge should be determined according to the specific conditions of the project, but should not be lower than 0.7 MPa. The maximum range of the vacuum gauge should be -0.1MPa.

    Outlet pipe

    ① A group of fire pumps shall be provided with no less than two water mains connected to the fire water supply ring network. When one of the water pipes is overhauled, the remaining water pipes shall still be able to supply the entire fire water supply design flow.

    ② A test water pipe of DN65 mm shall be set on the outlet pipe of each fire water pump, and drainage measures shall be taken. A set of fire pumps should be equipped with flow and pressure test devices in the fire pump room, and should meet the following requirements: When the flow rate of a single fire pump is not greater than 20 L / s and the design working pressure is not greater than 0.5 MPa, the pump set should be reserved Measurement flowmeter and pressure gauge interface, other pump sets should be equipped with pump set flow and pressure test devices. The measurement accuracy of the fire pump flow detection device should be 0.4, and 75% of the maximum range should be greater than 175% of the design flow value of the largest fire pump. The measurement accuracy of the fire pump pressure detection device should be 0.5, and 75% of the maximum range should be greater than 165% of the design value of the largest fire pump.

    ③ The outlet pipe of the fire water pump should be provided with check valve and open gate valve; when butterfly valve is used, it should be equipped with self-locking device; when the pipe diameter is greater than DN300mm, electric valve should be installed.

    ④ When the diameter of the outlet pipe is less than DN250, the velocity should be 1.5 ~ 2.0m / s; when the diameter is larger than DN250, it should be 2.0 ~ 2.5m / s. )

    ⑤ Silencer check valve, control valve and pressure gauge should be installed on the fire water pump outlet pipe; pressure gauge and pressure switch should also be installed on the main outlet pipe of the system; buffer devices should be installed when installing the pressure gauge. A cock should be installed between the pressure gauge and the buffer device; when there is no design requirement for the pressure gauge range, it should be 2 to 2.5 times the working pressure of the system. The diameter of the pressure gauge should not be less than 100 mm, and a pipe with a diameter of not less than 6 mm should be connected to the inlet and outlet pipes of the fire pump, and a shut-off valve should be provided.

    ⑥ The maximum range of the pressure gauge of the water pipe of the fire pump should not be less than twice its design working pressure, and should not be less than 1.6 MPa.

    The editor reminds you to avoid missed 2020 exam registration, payment, eligibility review, etc., you can book SMS reminders for free

    ”页面进行下载学习。 Global Network Alumni Tips: The above is the "2020 Comprehensive Test Capability of First-Class Fire Engineers" organized by the Global Network School's First-Class Fire Engineer Channel. For more simulated test questions, real questions, high-frequency test sites, and test preparation strategies, please click " Free " below. Download "page for download learning.

    share to: Edit: Sun Qing

    Bind phone number

    In accordance with the requirements of the "People's Republic of China Cyber Security Law" to strengthen the real-name authentication mechanism, and at the same time to provide a more comprehensive experience of product services, please bind your mobile phone number.

    Appointment made

    This live broadcast is a live lesson for paid students

    Please make a reservation after purchasing the course

    直播、听课。 Global Online School Mobile Class App broadcast live and listen to lessons. Insta Future!

    Android version

    download

    iPhone version

    download
    Global Small Over-Global WeChat Official WeChat Service Platform

    Resolving problems APP download

    Free live one-click lessons

    Registration and other manual services

    Back to top